Application Note
The contactor is the primary controller in a cooling
controls circuit. It is the switching device which activates
the compressor motor to pump refrigerant through the
system to provide cooling.
Contactors are used to break the power supply to the
compressor. Either 1 or 2 poles are needed for single
phase; 2 or 3 poles for 3 phase motors. Auxiliary
contacts may be used for interlock switching, fan loads
or crankcase heaters. If the contactor is selected with

an adequate current rating, the condenser fan may also
be wired in parallel with the compressor. Then the
condenser fan is energized whenever the compressor
is powered.
Checking Contactor Operation:
• Check contactor operation by switching the
contactor from the system controls.
• Make sure that the pressure and overload controls
can break the system circuit to prevent contactor
operation, if necessary.
• Check electrical conductance of the contacts.
• Check the voltage source to the coil.