How to Troubleshoot a Gas Furnace 905 403 9914

Natural gas  burns cleaner than  oil, and most gas furnaces present fewer operational difficulties than oil furnaces do. The problems that affect gas furnaces usually involve the furnace thermocouple, the pilot light, or some other partt of the electrical system.

Gas furnace and gas heaters have control shutoffs to prevent gas leaks, but they are not all fail safe. If you smell gas in your house, do not turn any lights on or off, and do not try to shut off the gas leading to the furnace. Get out of the house, leaving the door open, and  call the gas company or the fire department right away Do not re-enter your home.

 

 

On some gas furnaces and gas heaters, a plug type door covers the pilot light assembly. To gain access to the pilot burner, pull the door out of the furnace housing. On other units, remove the panel that covers the pilot and gas burners.

The pilot light controls, reset buttons, gas valves, and thermocouple are usually contained in an assembly at the front of the furnace. The furnace limit switch is located on the plenum  or main duct  on the upper housing of the furnace.

The Pilot Light

The pilot light on a gas furnace can go out because of drafts. To relight the pilot, follow the manufacturer's instructions exactly; they are usually fastened to the furnace. If instructions for relighting the pilot are not provided, follow this general procedure:

Step 1: Find pilot light assembly. It typically has a gas valve with on, off, and pilot settings.

Step 2: Turn valve to off and wait three minutes.

Step 3: Switch valve to pilot setting. Hold lighted match to pilot opening while you push reset button on pilot control panel. Keep this button depressed until pilot flame burns brightly, then set valve to on position.

Step 4: If pilot flame won't stay lit, opening may be clogged. Turn gas valve off, and clean opening with piece of fine wire. If it won't stay lit after several attempts, you may have faulty thermocouple. If pilot flame still won't stay lit, call professional service person.

Some furnaces have an electrical system to ignite the gas; in these systems there is no pilot light. Instead, an electric element heats up and ignites the burners. If this electric ignition system malfunctions, call a professional service person.

Replacing the Thermocouple

The thermocouple is a gas furnace component located near the pilot light burner. It is a safety device that shuts off the gas if the pilot light goes out or the electric igniter fails. Also see thermocouple circuit.

If the pilot light won't stay lit, the thermocouple may be faulty and should be adjusted or replaced. To adjust the thermocouple, you must tighten the thermocouple nut with a wrench. Take care not to apply too much pressure to the nut -- just tighten it slightly. Then try lighting the pilot. If the pilot won't stay lit, replace the thermocouple with a new one of the same type. Here's how to replace a thermocouple:

 

Step 1: Unscrew copper lead and connection nut inside threaded connection to gas line. Under mounting bracket at thermocouple tube, unscrew bracket nut that holds tube in place.

Step 2: Insert new thermocouple into hole in bracket. Be sure steel tube is up and copper lead is down. Under bracket, screw bracket nut over tube. Push connection nut to threaded connection where copper lead connects to gas line. Make sure connection is clean and dry.

Step 3: Tightly screw nut into place, but do not over-tighten. Both bracket nut and connection nut should be only a little tighter than if hand-tightened.
 

 

 

Limit Switch

The limit switch is a safety control switch located on the furnace just below the plenum. If the plenum gets too hot, the limit switch shuts off the burner. It also shuts off the blower when the temperature drops to a certain level after the burner has shut off. If the blower runs continuously, either the blower control on the thermostat has been set to the ON position or the limit control switch needs adjustment. Check the thermostat first. If the blower control has been set to ON, change it to AUTO; if the blower control is already on AUTO, the limit switch needs adjusting.

 

 

To adjust the switch, remove the control's cover. Under it is a toothed dial with one side marked LIMIT; don't touch this side. The other side of the control is marked FAN. There are two pointers on the fan side; the blower goes on at the upper pointer setting and turns off at the lower pointer setting. The pointers should be set about 25 degrees apart. Set the upper pointer at about 115 degrees Fahrenheit and the lower one at about 90 degrees Fahrenheit.

Burner Adjustment

The flames on the gas burner should be full and steady, with no sputtering and no trace of yellow. To adjust the flame height on the main burners, call a professional service person. To adjust the height of the pilot flame, turn the flame adjustment screw until the flame is from 11/2 to 2 inches high. The adjustment screw is located near the gas valve on the pilot assembly, if the control has this adjustment feature.

Gas Leaks

If you suspect leaks around the furnace unit, stir up a mixture of liquid detergent and water. Paint this mixture on the gas supply line along its connections and valves; the soapy water will bubble at any point where there's a leak. If you find a leak, try tightening the leaking connection with a pipe wrench, but be careful not to overtighten the connection. If the pipe connections or valves still leak, call a professional service person.

Back to our furnace service and furnace repair page. We do full furnace servicing in Mississauga Oakville Burlington